MasterGuard MG-CO/2000 Manuel de service Page 10

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 38
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 9
6 Control Unit, IGBT Inverter
MASTERGUARD Series SIII
UPS Systems from 60 to 800 kVA
8
MKA4CAT0UKSIII/Rev. 11-11/2004/UK
6.4 Total Harmonic Distortion
The inverter shall provide harmonic
neutralisation and filtering to limit the
THD to on the voltage to less than 3%
with a linear load. For reference non-
linear load (as defined by EN62040-3)
the THD shall be limited to less than 5%.
6.5 Neutral sizing
The sizing of the inverter neutral shall
be oversized on all ratings in order to
cope with the combination of
harmonics on the neutral wire when
driving single-phase reference non-
linear loads. From 60 to 200kVA the
inverter neutral is sized x 1.7 in relation
to the phase, while from 250 to
500kVA it is x 1.4 in relation to the
phase. Further oversizing could be
provided on demand.
6.6 Output power transformer
A dry type isolation transformer shall
be provided for the inverter AC output.
The transformer shall have an
insulation class H+. The temperature
limit of the insulation class of the
material shall not be exceeded when
operating at full load and within
ambient temperature limits.
6.7 Overload
The inverter shall be capable of
supplying an overload of 125% for 10
minutes and 150% for one minute of
the nominal power.
6.8 Inverter shutdown
In the event of an internal failure the
inverter shall be immediately
disconnected from the critical load and
shut down by the control unit. The UPS
device or the parallel-operated UPS
systems shall continue to supply the
load from the reserve supply without
interruption, if it is within permissible
limits.
6.9 Output voltage symmetry
The inverter shall guarantee the
symmetry of the output voltages at
±1% for balanced loads and ±3% for
100% unbalanced loads.
6.10 Phase displacement
The phase angle displacement
between the three-phase voltages
shall be:
•120°±1°for balanced loads
•120° ± 2° for unbalanced loads
(0, 0, 100%)
6.11 Short Circuit
The inverter short circuit capacity of
Series S
III for the first 10ms shall be
>200% for any short circuit
configuration. After the first 10ms, it
shall limit the current to >150% for 5s,
then it shall shut down.
6.12 Automatic upgrade of inverter
rated power
The inverter shall automatically
upgrade its power as a function of
ambient and operating temperatures,
as shown in Figure 5. In the most
common conditions (25°C) Series S
III
shall provide 10% more power than
nominal. In these conditions the
battery charge will be reduced
correspondingly.
For example:
@40°C, Idc tot. = 0.75(Idc inv) + 0.25
(Ibatt)
@25°C, Idc tot. = 0.83(Idc inv) + 0.17
(Ibatt)
6.1 AC voltage generation
From the DC voltage of the intermediate
circuit the inverter shall generate
sinusoidal AC voltage for the user load
on the basis of pulse-width modulation.
By means of the digital signal processor
of the control unit the inverter IGBTs
shall be controlled so that DC voltage is
divided up into pulsed voltage packets.
A transformer shall be provided at the
output of the inverter. Through this
transformer and a low-pass filter the
pulse-width modulated signal shall be
converted into sinusoidal AC voltage.
6.2 Voltage regulation
The inverter output voltage on the
three phases shall be individually
controlled to achieve the following
performances:
6.2.1 Steady state
The inverter steady state output
voltage shall not deviate by more than
±1% in a steady state condition for
input voltage and load variations within
the quoted limits.
6.2.2 Voltage transient response
The inverter transient voltage shall not
exceed Class 1 limits when subjected
to application or removal of 100% load
as defined by EN62040-3.
6.3 Frequency regulation
The inverter output frequency shall be
controlled to achieve the following
performances:
6.3.1 Steady state
The inverter steady-state output
frequency, when synchronised to
reserve supply, shall not deviate by
more than ±0.75% adjustable to
±1.5%, ±2.5%, ±6%.
6.3.2 Frequency slew rate
The frequency slew rate shall be 1Hz
per second.
6.3.3 Frequency Control
The output frequency of the inverter
shall be controlled by a quartz
oscillator which can be operated as a
free running unit or as a slave for
synchronised operation with a
separate AC source. The accuracy of
the frequency control shall be ±0.05%
when free-running.
Figure 5. Automatic power upgrade
15 25 30 40
115
112
110
105
100
Output Power
Ambient
Temperature
Tecnico-SIII-MG 10-11-2004 8:22 Pagina 8
Vue de la page 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 37 38

Commentaires sur ces manuels

Pas de commentaire